LC-060 LOW VOLTAGE CONTROLLER
Low Voltage Controllers enable users to safely operate the high-voltage lighting found in hospital and nursing home rooms with their pillow speaker or bed communication side rail. They’re tested and approved for use with all nurse call systems that use a switch with normally-open momentary dry contacts for auxiliaries.
FEATURES
- True universal voltage (120 to 277 VAC)
- For use with fluorescent, LED, and other lamp types
- Mounts in a lighting fixture
- Controls two loads independently (on/off), or two loads sequentially (on/off)
- For use with fluorescent, LED, and other lamp types
- Safe for use near medical equipment that is sensitive to electromagnetic noise
- Can be used to operate high-voltage circuits such as lights, electric doors, and drapes
- Can be controlled from a pillow speaker, bed side rail, or wall switch with normally-open momentary dry contacts
- Patent Pending
- UL/C-UL Listed to UL 508 • Compliant with FCC, Title 47 CFR 15 – Class B • RoHS compliant
- Industry-leading three year warranty
SPECIFICATIONS
LC-060 | |
---|---|
Input Voltage | 120-277 VAC, 60 Hz 277 VAC, 5 A, General Use 277 VAC, 5 A, Ballast RMS current should not exceed 5 amps per load |
Load Type | 277 VAC, 5 A, General Use per Load 277 VAC, 5 A, Ballast per Load Maximum total device current: 10 A |
Lamp Type | Fluorescent, LED, and other lamp types |
Output Voltage | 120-277 VAC, 60 Hz |
Output Devices | • Two 10 amp relays driven by low voltage microcontroller • ESD protected |
Dimming Control | NA |
Low Voltage Momentary Switch Requirements | Dry contacts, momentary, normally open, capable of switching 5 VDC @ 0.5 mA |
Switching Circuits Operation Voltage | 5 VDC @ 0.5 mA |
Power Supply Classification | Isolation from line voltage via a Class 2 transformer |
Ambient Operating Temperature Range | 32° to 140° F (0° to 60° C) |
External wires | • White/Black: 16 AWG stranded • All other wires: 18 AWG stranded |
Mounting | • Mounts next to a lighting ballast in lighting applications • May be mounted in a five gang masonry box with physical separation between high and low voltage |
Housing | .032" Galvanized Zinc-Plated Steel |
Dimensions | 6.75" with tabs (L) x 1.90" (W) x 1.20" (H) |
Warranty | Three Years |